Fronius PV inverter displaying a fault code?
Sometimes a problem indicated can be resolved without the need to call anyone out or replace hardware. If not then it might give a clue as to what the root cause could be.
- Check to see if your fault code is in the list below.
- All fault codes shown are manufacturer supplied.
- Follow any manufacturers advice indicated next to your error code.
- Many inverters will show an error indicating an internal failure, this usually means a replacement is required, call us for advice or a quote.
- If your inverter does not have a screen and is off-line you could try our home troubleshooting guide to try to get your solution working again.
- If all else fails we would be happy to take your call on 0330 345 3400



Repairs & Maintenance
- Domestic and Commercial, UK wide
- Grid Tie, Off Grid & Hybrid
- All manufacturers Inverter Errors Diagnosed & Resolved
- Energy Storage Systems
Additional Services
- Cloud & Monitoring faults investigated
- Solar Array Refits
- Bird & pest guard
- Free advice 0330 345 3400
Code |
Description |
Behaviour |
Corrective Measures |
STATE 102 |
AC voltage too high |
Following careful testing and when the grid conditions are within |
Check grid connections: If this STATE code keeps recurring contact |
STATE 103 |
AC voltage too low |
||
STATE 105 |
AC frequency too high |
||
STATE 106 |
AC frequency too low |
||
STATE 107 |
AC grid outside the permissible limits |
||
STATE 108 |
Stand-alone operation detected |
||
STATE 112 |
RCMU error |
Code |
Description |
Behaviour |
Corrective Measures |
STATE 301 |
Overcurrent (AC) |
Short-term interruption while feeding energy into the grid due to |
Fault is rectified automatically; if this STATE code is displayed constantly: |
STATE 302 |
Overcurrent (DC) |
||
STATE 303 |
DC module over temperature |
Short term interruption while feeding energy into the grid due to |
Purge openings for cooling air and heat sink if necessary; fault |
STATE 304 |
AC module over temperature |
||
STATE 305 |
No power being fed in, despite closed relay |
Short term interruption while feeding energy into the grid due to |
fault is rectified automatically; if this STATE code keeps |
STATE 306 |
PV output too low for feeding energy into the grid |
Short term interruption while feeding energy into the grid. |
Fault is rectified automatically; if this STATE code occurs when |
STATE 307 |
LOW PV VOLTAGE |
||
STATE 308 |
Intermediate circuit voltage too high |
Short term interruption while feeding energy into the grid. The |
Fault is rectified automatically; if this STATE code is displayed constantly: |
STATE 309 |
DC input voltage MPPT 1 too high |
||
STATE 311 |
Polarity of DC strings reversed |
||
STATE 313 |
DC input voltage MPPT 2 too high |
||
STATE 314 |
Current sensor calibration timeout |
Short term interruption while feeding energy into the grid. The |
Fault is rectified automatically; if this STATE code is displayed constantly: |
STATE 315 |
AC current sensor erro |
||
STATE 316 |
Interrupt Check fail |
||
STATE 325 |
Overtemperature in the connection area |
||
STATE 326 |
Fan 1 error |
||
STATE 327 |
Fan 2 error |
Code |
Description |
Behaviour |
Corrective Measures |
STATE 401 |
No communication possible with the power stage set |
The inverter will automatically attempt to connect again and, if |
If the STATE code is displayed constantly contact your local |
STATE 406 |
AC module temperature sensor faulty (L1) |
||
STATE 407 |
AC module temperature sensor faulty (L2) |
||
STATE 408 |
DC component measured in the grid too high |
||
STATE 412 |
Fixed voltage mode has been selected instead of MPP voltage mode |
– |
If this STATE code persists contact your solar power system |
STATE 415 |
Safety cut out via option card or RECERBO has triggered |
The inverter is not feeding any energy into the grid. |
If the STATE code is displayed constantly contact your local Fronius |
STATE 416 |
No communication possible between power stage set and control |
The inverter will automatically attempt to reconnect again and, if |
|
STATE 417 |
Hardware ID problem |
Update the inverter firmware; if the STATE code is displayed constantly |
|
STATE 419 |
Unique ID conflict |
||
STATE 420 |
No communication possible with the Hybrid manager |
||
STATE 421 |
HID range error |
||
STATE 425 |
No communication with the power stage set possible |
||
STATE 426-428 |
Possible hardware fault |
||
STATE 431 |
Software problem |
The inverter is not feeding any energy into the grid. |
Carry out an AC reset (switch the AC circuit breaker off and on); |
STATE 436 |
Functional incompatibility (one or more PC boards in the inverter |
The inverter will automatically attempt to connect again and, if |
Update the inverter firmware; if the STATE code is displayed constantly |
STATE 437 |
Power stage set problem |
||
STATE 438 |
Functional incompatibility (one or more PC boards in the inverter |
||
STATE 443 |
Intermediate circuit voltage too low or asymmetric |
The inverter is not feeding any energy into the grid. |
If the status code is displayed constantly contact your local |
STATE 445 |
– Compatability error (e.g. due to replacement of a PC board) |
The inverter is not feeding any energy into the grid for safety |
Update the inverter firmware; if the STATE code is displayed constantly |
STATE 447 |
Insulation fault |
If this status code is displayed constantly: notify a local |
|
STATE 448 |
Neutral conductor not connected |
||
STATE 450 |
Guard cannot be found |
||
STATE 451 |
Memory error detected |
The inverter will automatically attempt to connect again, and if |
If the STATE code is displayed constantly: notify your local |
STATE 452 |
Communication error between the processors |
||
STATE 453 |
Grid voltage and power stage set are incompatible |
||
STATE 454 |
Grid frequency and power stage set are incompatible |
||
STATE 456 |
Anti-islanding function is no longer implemented correctly |
||
STATE 457 |
Grid relay sticking or the neutral conductor ground voltage is too |
The inverter is not feeding any energy into the grid. |
Check the grounding (the neutral conductor ground voltage must be |
STATE 458 |
Error when recording the measuring signal |
Contact your local Fronius Service Partner. |
|
STATE 459 |
Error when recording the measuring signal for the insulation test |
||
STATE 460 |
Reference voltage source for the digital signal processor (DSP) is |
||
STATE 461 |
Fault in the DSP data memory |
||
STATE 462 |
Error with DC feed monitoring routine |
||
STATE 463 |
Reversed AC polarity, AC connector inserted incorrectly |
||
STATE 474 |
RCMU sensor faulty |
||
STATE 475 |
Solar panel ground fault, insulation fault (connection between |
||
STATE 476 |
Driver supply voltage too low |
||
STATE 480, 481 |
Functional incompatibility (one or more PC boards in the inverter |
Update the inverter firmware; if the STATE code is displayed constantly |
|
STATE 482 |
Setup after the initial start-up was interrupted |
Perform AC reset (turn AC circuit breaker off and on), complete |
|
STATE 483 |
Voltage UDC fixed on MPP2 string out of limits |
Check the MPP settings; if the status code is displayed constantly |
|
STATE 485 |
CAN transmit buffer is full |
Carry out an AC reset (turn AC circuit breaker off and on), if the |
Code |
Description |
Behaviour |
Corrective Measures |
STATE 502 |
Insulation error on the solar panels |
Warning message is shown on the display |
If this STATE code keeps recurring, contact your solar power |
STATE 509 |
No energy fed into the grid in the past 24 hours |
Acknowledge STATE code; check whether all the conditions for the |
|
STATE 515 |
No communication with filter possible |
If the status code is displayed constantly notify your local |
|
STATE 516 |
No communication possible with the storage unit |
Storage unit warning message. |
|
STATE 517 |
Power derating caused by too high a temperature |
When power derating occurs, a warning message is shown on the |
Purge cooling air openings and heat sink if necessary; fault is |
STATE 518 |
Internal DSP malfunction |
Warning message on the display |
If this STATE code keeps recurring contact your solar power system |
STATE 519 |
No communication possible with the storage unit |
Storage unit warning message |
|
STATE 520 |
No energy fed into the grid by MPPT1 in the past 24 hours |
Warning message is shown on the display |
Acknowledge status code; check whether all the conditions for the |
STATE 522 |
DC low string 1 |
Warning message on the display |
|
STATE 523 |
DC low string 2 |
||
STATE 558, 559 |
Functional incompatibility (one or more PC boards in the inverter |
Update the inverter firmware;if the STATE code is displayed constantly |
|
STATE 560 |
Derating caused by over-frequency |
This STATE code is displayed when the grid frequency becomes |
As soon as the grid frequency is back within the permissible range |
STATE 564 |
Functional incompatibility (one or more PC boards in the inverter |
Warning message on the display |
Update the inverter firmware if the STATE code is displayed constantly |
STATE 566 |
Arc detector switched off (e.g. during external arc monitoring) |
The STATE code is displayed every day until the arc detector is |
No error |
STATE 567 |
Grid Voltage Dependent Power Reduction is active |
This state code is a warning informing you that the Grid Voltage |
Acknowledge status code; if this STATE 567 code keeps recurring |
Code |
Description |
Behaviour |
Corrective Measures |
STATE 601 |
CAN bus is full |
The inverter is not feeding any energy into the grid. |
Update the inverter firmware; if the STATE code is displayed constantly |
STATE 603 |
AC module temperature sensor faulty (L3) |
The inverter will automatically attempt to connect again and, if |
If this STATE code keeps recurring contact your solar power system |
STATE 604 |
DC module temperature sensor faulty |
||
STATE 607 |
RCMU error |
The inverter is not feeding any energy into the grid. |
Reset status code by pressing ‘Enter’. The inverter resumes the |
STATE 608 |
Functional incompatibility (one or more PC boards in the inverter |
Update the inverter firmware; if the STATE code is displayed constantly |
Code |
Description |
Behaviour |
Corrective Measures |
STATE 701-716 |
Provides information about the internal processor status |
Warning message is shown on the display |
If the STATE code is displayed constantly notify your local |
STATE 721 |
EEPROM has been re-initialised |
Acknowledge STATE code; If the STATE code is displayed constantly |
|
STATE 722-730 |
Provides information about the internal processor status |
If the STATE code is displayed constantly contact your local Fronius |
|
STATE 731 |
Initialisation error – USB flash drive is not supported |
Check or replace USB flash drive. Check the file system on the USB |
|
STATE 732 |
Initialisation erro – Over current on USB stick |
||
STATE 733 |
No USB flash drive connected |
Connect or check the USB flash drive. If STATE code is displayed constantly |
|
STATE 734 |
Update file not recognised or not present |
Check update file (e.g. for correct file name). If STATE code is |
|
STATE 735 |
Update file does not match the device, update file too old |
Warning message appears on the display, update process is |
Check the update file; if the STATE code is displayed constantly |
STATE 736 |
Write or read error occurred |
Warning message is shown on the display |
Check USB flash drive and the data contained on it or replace USB |
STATE 737 |
File could not be opened |
Remove and then reinsert USB flash drive; check or replace USB |
|
STATE 738 |
Log file cannot be saved (e.g. USB flash drive is write protected |
Create storage space, remove write protection, check, or replace |
|
STATE 740 |
Initialisation error-error in file system on USB flash drive |
Check USB flash drive; reformat on PC for FAT12, FAT16 or FAT32. |
|
STATE 741 |
Error during recording of logging data |
Remove and then reinsert USB flash drive; check or replace USB |
|
STATE 743 |
Error occurred during update process |
Repeat the update process, check USB stick. If STATE code is |
|
STATE 745 |
Update file corrupt |
Warning message appears on the display, update process is interrupted. |
Re-download update file. If STATE code is displayed constantly |
STATE 746 |
Error occurred during update process |
Wait for 2 minutes, then start the update again. If STATE code is |
|
STATE 751 |
Time lost |
Warning message is shown on the display |
Reset the time and date on the inverter. Check update file (e.g. |
STATE 752 |
Real Time Clock module communication error |
||
STATE 753 |
Internal error: Real Time Clock module is in emergency mode |
Time may be inaccurate or lost (feeding energy into the grid |
|
STATE 754-755 |
Provides information about the processor status |
Warning message on the display |
If STATE code is displayed constantly contact your local Fronius |
STATE 757 |
Hardware error in the Real Time Clock module |
Error message is shown on the display; the inverter is not feeding |
|
STATE 758 |
Internal error: Real Time Clock module is in emergency mode |
Time may be inaccurate or lost (feeding energy into the grid |
Reset time and date on the inverter |
STATE 760 |
Internal hardware error |
Error message is shown on the display. |
If STATE code is displayed constantly contact your local Fronius |
STATE 761-765 |
Provides information about the internal processor status |
Warning message is shown on the display. |
|
STATE 766 |
Emergency power de-rating has been activated |
Error message is shown on the display. |
|
STATE 767 |
Provides information about the internal processor status |
Warning message is shown on the display. |
|
STATE 768 |
Different power limitation in the hardware modules |
||
STATE 772 |
Storage unit not available |
||
STATE 773 |
Software update group 0 (invalid country setup) |
||
STATE 775 |
PMC power stage set not available |
Warning message is shown on the display. |
Press ‘Enter’ key to acknowledge error. If STATE code is displayed |
STATE 776 |
Invalid device type |
||
STATE 781-794 |
Provides information about the internal processor status |
Warning message is shown on the display. |
If STATE code is displayed constantly contact your local Fronius |
Remember, our engineering staff are never more than an hour away and can have you back up and running in no time
Give us a call, we will take your details, arrange an engineer, and aim to resolve your solar problem as soon as possible.
Photos are always an effective way to show us your problem too.
Call Bolido Solar on 0330 345 3400 or use the inquiry form and we will call you back