Solar PV Inverter Errors – SMA

SMA PV inverter displaying a fault code?

Sometimes a problem indicated can be resolved without the need to call anyone out or replace hardware. If not then it might give a clue as to what the root cause could be.

  • Check to see if your fault code is in the list below.
  • All fault codes shown are manufacturer supplied.
  • Follow any manufacturers advice indicated next to your error code.
  • Many inverters will show an error indicating an internal failure, this usually means a replacement is required, call us for advice or a quote.
  • If your inverter does not have a screen and is off-line you could try our home troubleshooting guide to try to get your solution working again.
  • If all else fails we would be happy to take your call on 0330 345 3400
Commercial inverter fitting service
maintenance-1
Domestic inverter fitting service without cloud connection

Repairs & Maintenance

Additional Services

Code

Description & Corrective Measures

101

102

103

Grid fault

The grid voltage or grid impedance at the connection point of the inverter is too high. The inverter has disconnected from the utility grid.

Corrective measures:

Check whether the grid voltage at the connection point of the inverter is permanently in the permissible range.

If the grid voltage is outside the permissible range due to local grid conditions, contact the grid operator. The grid operator must agree with an adjustment of the voltage at the feed-in point or with a change of the monitored operating limits.

If the grid voltage is permanently within the permissible range and this message is still displayed, contact your solution maintainer.

202

203

205

Grid fault

The utility grid has been disconnected, the AC cable is damaged or the grid voltage at the connection point of the inverter is too low. The inverter has disconnected from the utility grid.

Corrective measures:

Ensure that the circuit breaker is switched on.

Ensure that the AC cable is not damaged and that it is connected correctly.

Ensure that the country data set has been configured correctly.

Check whether the grid voltage at the connection point of the inverter is permanently in the permissible range.

If the grid voltage is outside the permissible range due to local grid conditions, contact the grid operator. The grid operator must agree with an adjustment of the voltage at the feed-in point or with a change of the monitored operating limits.

If the grid voltage is permanently within the permissible range and this message is still displayed, contact the Service.

301

Grid fault

The ten-minute average value of the grid voltage is no longer within the permissible range. The grid voltage or grid impedance at the connection point is too high. The inverter disconnects from the utility grid to maintain power quality.

Corrective measures:

During the feed-in operation, check whether the grid voltage at the connection point of the inverter is permanently in the permissible range.

If the grid voltage is outside the permissible range due to local grid conditions, contact the grid operator. The grid operator must agree with an adjustment of the voltage at the feed-in point or with a change of the monitored operating limits.

If the grid voltage is permanently within the permissible range and this message is still displayed, contact your solution maintainer.

302

Active power limit AC voltage

The inverter has reduced its power due to a too-high grid voltage to ensure grid stability.

Corrective measures:

If possible, check the grid voltage and observe how often fluctuations occur. If fluctuations occur frequently and this message is displayed often, contact the grid operator and request approval to change the operating parameters of the inverter. If the grid operator gives his approval, discuss any changes to the operating parameters with the Service.

401

404

Grid fault

The inverter has disconnected from the utility grid. A stand-alone grid or a very large change in the power frequency was detected.

Corrective measures:

Check the grid connection for significant short-term frequency fluctuations.

501

Grid fault

The power frequency is not within the permissible range. The inverter has disconnected from the utility grid.

Corrective measures:

If possible, check the power frequency and observe how often fluctuations occur.

If fluctuations occur frequently and this message is displayed often, contact the grid operator and request approval to change the operating parameters of the inverter.

If the grid operator gives his approval, discuss any changes to the operating parameters with the Service.

601

Grid fault

The inverter has detected an excessively high proportion of direct current in the grid current.

Corrective measures:

Check the grid connection for direct current.

If this message is displayed frequently, contact the grid operator and check whether the monitoring threshold on the inverter can be raised.

701

Frequency not permitted > Check parameter

The power frequency is not within the permissible range. The inverter has disconnected from the utility grid.

Corrective measures:

If possible, check the power frequency and observe how often fluctuations occur.

If fluctuations occur frequently and this message is displayed often, contact the grid operator and request approval to change the operating parameters of the inverter.

If the grid operator gives his approval, discuss any changes to the operating parameters with the Service.

901

PE connection missing > Check connection

The grounding conductor is not correctly connected.

Corrective measures:

Ensure that the grounding conductor is correctly connected.

1001

L / N swapped > Check connection

The connection of L and N is swapped.

Corrective measures:

Ensure that L and N are correctly connected.

1101

Installation fault > Check connection

A second line conductor is connected to N.

Corrective measures:

Connect the neutral conductor to N.

1302

Waiting for grid voltage > Installation failure grid connection > Check grid and fuses

L or N not connected.

Corrective measures:

Ensure that L and N are connected.

Ensure that the circuit breaker is switched on.

Ensure that the AC cable is not damaged and that it is connected correctly.

1501

Reconnection fault grid

The changed country data set or the value of a parameter you have set does not correspond to the local requirements. The inverter cannot connect to the utility grid.

Corrective measures:

Ensure that the country data set has been configured correctly. To do this, select the parameter Set country standard and check the value.

3301

3302

3303

Unstable operation

There is not enough power at the DC input of the inverter for stable operation. The inverter cannot connect to the utility grid.

Corrective measures:

Ensure that the PV array is designed correctly.

Ensure that the PV array is not covered by snow or otherwise shaded.

Ensure that the PV array is free of errors.

3401

3402

3407

DC overvoltage > Disconnect generator

Overvoltage at the DC input. This can destroy the inverter.

This message is signalized additionally by rapid flashing of the LEDs.

Corrective measures:

Immediately disconnect the inverter from all voltage sources.

Check whether the DC voltage is below the maximum input voltage of the inverter. If the DC voltage is below the maximum input voltage of the inverter, reconnect the DC connectors to the inverter.

If the DC voltage exceeds the maximum input voltage of the inverter, ensure that the PV array has been correctly rated or contact the installer of the PV array.

If this message is repeated frequently, contact the Service.

3501

Insulation failure > Check generator

The inverter has detected a ground fault in the PV array.

Corrective measures:

Check the PV system for ground faults.

3701

Residual current too high > Check generator

The inverter has detected a residual current due to temporary grounding of the PV array.

Corrective measures:

Check the PV system for ground faults.

3801

3802

3805

DC overcurrent > Check generator

Overcurrent at the DC input. The inverter briefly interrupts feed-in operation.

Corrective measures:

If this message is displayed frequently, ensure that the PV array has been correctly rated and wired.

3901

3902

Waiting for DC start conditions > Start conditions not met

The feed-in conditions for the utility grid are not yet fulfilled.

Corrective measures:

Ensure that the PV array is not covered by snow or otherwise shaded.

Wait for higher irradiation.

If this message is displayed frequently in the morning, increase the voltage limit for starting grid feed-in. Change the parameter Critical voltage to start feed-in.

If this message is displayed frequently with medium irradiation, ensure that the PV array is correctly rated.

4011

Bridged strings determined

The DC inputs A and B are connected in parallel.

4012

No bridged strings determined

The DC inputs A and B are not connected in parallel.

6002-6412

Self-diagnosis > Interference device

The cause must be determined by the Service.

Corrective measures:

Contact the Service.

6501

6502

6509

Self-diagnosis > Overtemperature

The inverter has switched off due to excessive temperature.

Corrective measures:

Clean the cooling fins on the rear of the enclosure and the air ducts on the top using a soft brush.

Ensure that the inverter has sufficient ventilation.

Ensure that the ambient temperature does not exceed +40 °.

Ensure that the inverter is not exposed to direct solar irradiation.

6512

Minimum operating temperature not reached

The inverter will only recommence grid feed-in once the temperature has reached at least −25°C.

6602

6603

6604

Self-diagnosis > Overload

The cause must be determined by the Service.

Corrective measures:

Contact the Service.

6801

6802

Self-diagnosis > Input A defective

Corrective measures:

Check whether a string is connected to input A.

Contact the service.

6901

6902

Self-diagnosis > Input B defective

Corrective measures:

Check whether a string is connected to input B.

Contact the service.

6701

6702

Communication disturbed

Error in the communication processor, the inverter continues feeding in, however. The cause must be determined by the Service.

Corrective measures:

If this message is displayed frequently, contact the Service.

7102

Parameter file not found or defective

The parameter file was not found or is defective. The update failed. The inverter continues to feed in.

Corrective measures:

Copy the parameter file to the correct folder again.

7105

Parameter setting failed

Parameters could not be set using the memory card. The inverter continues to feed in.

Corrective measures:

Ensure that the parameters are set correctly.

Ensure that the SMA Grid Guard code is available.

7106

Update file defective

The update file is defective. The update failed. The inverter continues to feed in.

7110

No update file found

No new update file was found on the SD memory card. The update failed. The inverter continues to feed in.

7112

Update file successfully copied

7113

The memory card is full or write-protected

7201 to 7202

Data storage not possible

7303

Update main CPU failed

The cause must be determined by the Service.

Corrective measures:

Contact the Service.

7320

The device was successfully updated

The firmware update was completed successfully.

7330

Condition test failed

The testing of the update conditions was successful. The firmware update package is suitable for this inverter.

7331

Update transport started

Update file is being copied.

7332

Update transport successful

Update file was copied successfully to the inverter’s internal memory.

7333

Update transport failed

Update file could not be copied to the inverter’s internal memory. In the event of connection with the inverter via WLAN, a poor connection quality can be the cause.

Corrective measures:

Retry update.

For WLAN connection: Improve the WLAN connection quality (e.g., via WLAN repeater) or establish a connection with the inverter via Ethernet.

If this message is displayed again, contact the Service.

7341

Update Bootloader

The inverter is performing a bootloader update.

7342

Update Bootloader failed

The bootloader update failed.

Corrective measures:

Retry update.

If this message is displayed again, contact the Service.

7347

Incompatible file

The configuration file is not suitable for this inverter.

Corrective measures:

Ensure that the selected configuration file is suitable for this inverter.

Retry import.

7348

Incorrect file format

The configuration file is not of the required format or is damaged.

Corrective measures:

Ensure that the selected configuration file is of the required format and is not damaged.

Retry import.

7349

Incorrect login rights for configuration file

The user group logged in does not have the user rights necessary to be able to import a configuration.

Corrective measures:

Log in as Installer.

Import configuration file again.

7350

Transfer of a configuration file has started

The configuration file is being transferred.

7351

Update WLAN

The inverter is updating the WLAN module.

7352

Update of WLAN not successful

The update of the WLAN module failed.

Corrective measures:

Retry update.

If this message is displayed again, contact the Service.

7353

Update time zone database

The inverter is updating the time zone database.

7354

Update of time zone database not successful

The update of the time zone database failed.

Corrective measures:

Retry update.

If this message is displayed again, contact the Service.

7355

Update WebUI

The inverter is updating the inverter user interface.

7356

Update of the WebUI not successful

The update of the inverter user interface failed.

Corrective measures:

Retry update.

If this message is displayed again, contact the Service.

7500 to 7501

Fan fault > Check inverter electr. and fan

Corrective measures:

Contact the Service.

7619

Communication fault with meter unit > Check communication to meter

The inverter is not receiving any data from the energy meter.

Corrective measures:

Ensure that the energy meter is correctly integrated into the same network as the inverter (see energy meter manual).

For WLAN connection: Improve the WLAN connection quality (e.g., via WLAN repeater) or connect the inverter with the DHCP server (router) via Ethernet.

7702

Interference device

The cause must be determined by the Service.

Corrective measures:

Contact the Service.

8003

Active power limit Temperature

The inverter has reduced its power output for more than ten minutes due to excessive temperature.

Corrective measures:

Clean the cooling fins on the rear of the enclosure and the air ducts on the top using a soft brush.

Ensure that the inverter has sufficient ventilation.

Ensure that the ambient temperature does not exceed +40 °.

Ensure that the inverter is not exposed to direct solar irradiation.

8101 to 8104

Communication disturbed

The cause must be determined by the Service.

Corrective measures:

Contact the Service.

9002

SMA Grid Guard code invalid

The SMA Grid Guard code entered is incorrect. The operating parameters are still protected and cannot be changed.

Corrective measures:

Enter the correct SMA Grid Guard code.

9003

Grid parameter locked

Changes to the grid parameters are now blocked. In order to be able to make changes to the grid parameters, from now on you must log in using the SMA Grid Guard code.

9005

Changing of grid parameters not possible > Ensure DC supply

This error can have the following causes:

The parameters to be changed are protected.

The DC voltage at the DC input is not sufficient to run the main CPU.

Corrective measures:

Enter the SMA Grid Guard code.

Ensure that at least the DC start voltage is available (green LED is flashing, pulsing or glowing).

9007

Abort self-test

The self-test (Italy only) was terminated.

Corrective measures:

Ensure that the AC connection is correct.

Restart the self-test.

10108

Time adjusted / old time

10109

Time adjusted / new time

10110

Time synchronization failed: |tn0|

No time information could be called up from the set NTP server.

Corrective measures:

Ensure that the NTP server was configured correctly.

Ensure that the inverter is integrated into a local network with Internet connection.

10118

Parameter upload complete

The configuration file was loaded successfully.

10248

[Interface]: network busy

The network is busy. Data exchange between the devices is not at an optimum and is greatly delayed.

Corrective measures:

Increase the query intervals.

If necessary, reduce the number of devices in the network.

10249

[Interface]: network overloaded

The network is overloaded. There is no data exchange between the devices.

Corrective measures:

Reduce the number of devices in the network.

If necessary, increase the data query intervals.

10250

[Interface]: package error rate [ok / high]

The package error rate has changed. If the package error rate is high, the network is overloaded or the connection to the network switch or DHCP server (router) is disturbed.

Corrective measures if the package error rate is high:

Ensure that with an Ethernet connection, the network cable and the network connector are not damaged and that the network connectors are correctly plugged.

If necessary, increase the data query intervals.

If necessary, reduce the number of devices in the network.

10251

[Interface]: communication status goes to [OK / Warning / Error / Not connected]

The communication status to the network switch or DHCP server (router) has changed. An additional error message may be displayed.

10252

[Interface]: communication disrupted

There is no valid signal on the network line.

Corrective measures:

Ensure that with an Ethernet connection, the network cable and the network connector are not damaged and that the network connectors are correctly plugged.

Ensure that the DHCP server (router) and any network switches are signalizing correct operation.

10253

[Interface]: connection speed goes to [100 Mbit / 10 Mbit]

The data transfer rate has changed. The cause for the status [10 Mbit] can be a defective plug, a defective cable or the pulling or plugging of the network connector.

Corrective measures if the status is [10 Mbit]:

Ensure that with an Ethernet connection, the network cable and the network connector are not damaged and that the network connectors are correctly plugged.

Ensure that the DHCP server (router) and any network switches are signalizing correct operation.

10254

[Interface]: duplex mode goes to [Full / Half]

The duplex mode (data transfer mode) has changed. The cause for the status [Half] can be a defective plug, a defective cable or the pulling or plugging of the network connector.

Corrective measures if the status is [Half]:

Ensure that with an Ethernet connection, the network cable and the network connector are not damaged and that the network connectors are correctly plugged.

Ensure that the DHCP server (router) and any network switches are signalizing correct operation.

10255

[Interface]: Network load OK

The network load has returned to a normal range after being busy.

10282

[User group]-Login via [protocol] locked

After several incorrect login attempts, login has been blocked for a limited time. In this case, the User login will be blocked for 15 minutes, the Grid Guard login for 12 hours.

Corrective measures:

Wait until the given time has expired and then retry login.

10283

WLAN module faulty

The WLAN module integrated in the inverter is defective.

Corrective measures:

Contact the Service.

10284

No WLAN connection possible

The inverter does not currently have a WLAN connection to the selected network.

Corrective measures:

Ensure that the SSID, the WLAN password and the encryption method have been entered correctly. The encryption method is specified by your WLAN router or WLAN Access Point and can be changed there.

Ensure that the WLAN router or WLAN Access Point is in range and is signalizing correct operation.

If this message is displayed often, improve the WLAN connection by using a WLAN repeater.

10285

WLAN connection established

Connection to the selected WLAN network has been established.

10286

WLAN connection lost

The inverter has lost WLAN connection to the selected network.

Corrective measures:

Ensure that the WLAN router or WLAN Access Point is still active.

Ensure that the WLAN router or WLAN Access Point is in range and is signalizing correct operation.

If this message is displayed often, improve the WLAN connection by using a WLAN repeater.

10339

Webconnect enabled

The Webconnect function has been enabled.

10340

Webconnect disabled

The Webconnect function has been disabled.

10502

Active power limit AC frequency

The inverter has reduced its power due to a too-high power frequency to ensure grid stability.

Corrective measures:

If possible, check the power frequency and observe how often fluctuations occur. If fluctuations occur frequently and this message is displayed often, contact the grid operator and request approval to change the operating parameters of the inverter. If the grid operator gives his approval, discuss any changes to the operating parameters with the Service.

10901

Self-test start [xx]

The self-test is running.

10902

Current disconnection limit for voltage increase protection [xxx] V

Preliminary result of the self-test

10903

Current disconnection limit for voltage monitoring lower maximum threshold [xxx] V

Preliminary result of the self-test

10904

Current disconnection limit for voltage monitoring upper minimum threshold [xxx] V

Preliminary result of the self-test

10905

Current disconnection limit for voltage monitoring middle minimum threshold [xxx] V

Preliminary result of the self-test

10906

Current disconnection limit for frequency monitoring switchable maximum threshold |xxx| Hz

Preliminary result of the self-test

10907

Current disconnection limit for frequency monitoring switchable minimum threshold [xxx] Hz

Preliminary result of the self-test

10908

Current disconnection limit for frequency monitoring switchable minimum threshold [xxx] Hz

Preliminary result of the self-test

10909

Current disconnection limit for frequency monitoring upper minimum threshold [xxx] Hz

Preliminary result of the self-test

10910

Measured disconnection threshold for the running test point [xxx] [xx]

Preliminary result of the self-test

10911

Measured disconnection threshold for the running test point [xxx] [xx]

Preliminary result of the self-test

10912

Measured disconnection time for the running test point [xx] s

Preliminary result of the self-test

27103

Set parameter

The parameter changes are being adopted.

27104

Parameters set successfully

The parameter changes were successfully adopted.

27107

Update file OK

The update file found is valid.

27301

Update communication

The inverter is updating the communication component.

27302

Update main CPU

The inverter is updating the inverter component.

27312

Update completed

The inverter has successfully completed the update.

29001

Installer code valid

The entered Grid Guard code is valid. Protected parameters have now been unlocked and you can adjust the parameters. The parameters will be automatically locked again after ten feed-in hours.

29004

Grid parameters unchanged

Changing the grid parameters is not possible.

Remember, our engineering staff are never more than an hour away and can have you back up and running in no time

Give us a call, we will take your details, arrange an engineer, and aim to resolve your solar problem as soon as possible.

Photos are always an effective way to show us your problem too.

 

Call Bolido Solar on 0330 345 3400 or use the inquiry form and we will call you back

Tim Foreman
Tim Foreman
4 weeks ago
Read More
Scott designed and carried out a PV cell installation recently. The quote was competitive and the correspondence quick and concise. The fitting was arranged within a week, once the specification was agreed. On site, assisted by Mike, they were helpful and friendly and despite a difficult routing for the cable they came up with a successful solution. The end result is a very tidy, externally & internally, solar fit for the property. Great job and communication throughout, overall I'm very satisfied with their service and would recommend them.
Elspeth Robinson
Elspeth Robinson
3 weeks ago
Read More
Thank you for your outstanding service we received with regards to our solar panels which needed a new inverter. In next to no time, the problem was identified, a replacement ordered, delivered and fitted and the solar panels immediately started to record our readings. I have 100% confidence in recommending Bolido!
Greg Bertrum
Greg Bertrum
2 weeks ago
Read More
Very refreshing to get such a thorough and decent service. My company, a solar installations company needed technical assistance on-site for two projects. We also needed help with some of our own IT systems particularly with providing secure internet and network access between us and our clients, primarily for sharing power generation data but also increasingly alongside power usage data. Scott and his team were great with our clients and we just left to it. They were also quick to understand exactly what we wanted to achieve. They carried out all of the work, quickly, cleanly and with the minimum of fuss. We are now in a great position network and IT wise, moving forward we are confident in being able to service bigger clients with however sophisticated a network solution they might require. Highly recommend this company.
Little Miss Psycho
Little Miss Psycho
1 week ago
Read More
Fantastic and thorough service from these guys following birds nesting and ruining the connections on our solar installation. Great communications throughout, and friendly professional service.